7SR18 Solkor Settings Guide
Unrestricted
Page 8 of 44 © 2016 Siemens Protection Devices Limited
Description Range Default
Gn 87HS-2 Element Disabled, Enabled Disabled
Gn 87HS-2 Setting 1, 2 ... 29, 30 20xIn
Gn 87HS-2 Delay 0, 0.005 ... 59.9, 60 0s
7 DIFFERENTIAL IT
7.1 87R
Description Range Default
Gn 87R Element Disabled, Enabled Disabled
Gn 87R Delay 0, 0.005 ... 59.9, 60 0.005s
8 CURRENT PROT'N
8.1 PHASE OVERCURRENT
Description Range Default
Gn 67 Char Angle -95, -94 ... 94, 95 45deg
Gn 67 Minimum Voltage 1, 1.5 ... 19.5, 20 1V
Gn 67 2-out-of-3 Logic Enabled, Disabled Disabled
Gn 50 Measurement RMS, Fundamental RMS
Gn 51 Measurement RMS, Fundamental RMS
8.1.1 51-1
Description Range Default
Gn 51-1 Element Disabled, Enabled Enabled
Gn 51-1 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 51-1 Setting 0.05, 0.06 ... 2.49, 2.5 1xIn
Gn 51-1 Char DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51-1 Time Mult (IEC/ANSI) 0.025, 0.03 ... 99, 100 1
Gn 51-1 Delay (DTL) 0, 0.01 ... 19.99, 20 5s
Gn 51-1 Min Operate Time 0, 0.01 ... 19.99, 20 0s
Gn 51-1 Follower DTL 0, 0.01 ... 19.99, 20 0s
Gn 51-1 Reset (IEC/ANSI) Decaying, 0 ... 59, 60 0s
Gn 51-1 VTS Action Off, Inhibit, Non-Dir Off
Gn 51-1 Inrush Action Off, Inhibit Off
8.1.2 51-2
Description Range Default
Gn 51-2 Element Disabled, Enabled Disabled
Gn 51-2 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 51-2 Setting 0.05, 0.06 ... 2.49, 2.5 1xIn
Gn 51-2 Char DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI