7SR18 Solkor Settings Guide
Unrestricted
Page 12 of 44 © 2016 Siemens Protection Devices Limited
11 DERIVED E/F
Description Range Default
Gn 67N Polarizing Quantity ZPS, NPS ZPS
Gn 67N Char Angle -95, -94 ... 94, 95 -15deg
Gn 67N Minimum Voltage 0.33, 0.5, 1, 1.5, 2, 2.5, 3 0.33V
11.1 51N-1
Description Range Default
Gn 51N-1 Element Disabled, Enabled Disabled
Gn 51N-1 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 51N-1 Setting 0.05, 0.06 ... 2.49, 2.5 0.5xIn
Gn 51N-1 Char DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51N-1 Time Mult (IEC/ANSI) 0.025, 0.03 ... 99, 100 1
Gn 51N-1 Delay (DTL) 0, 0.01 ... 19.99, 20 5s
Gn 51N-1 Min Operate Time 0, 0.01 ... 19.99, 20 0s
Gn 51N-1 Follower DTL 0, 0.01 ... 19.99, 20 0s
Gn 51N-1 Reset (IEC/ANSI) Decaying, 0 ... 59, 60 0s
Gn 51N-1 VTS Action Off, Inhibit, Non-Dir Off
Gn 51N-1 Inrush Action Off, Inhibit Off
11.2 51N-2
Description Range Default
Gn 51N-2 Element Disabled, Enabled Disabled
Gn 51N-2 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 51N-2 Setting 0.05, 0.06 ... 2.49, 2.5 0.5xIn
Gn 51N-2 Char DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51N-2 Time Mult (IEC/ANSI) 0.025, 0.03 ... 99, 100 1
Gn 51N-2 Delay (DTL) 0, 0.01 ... 19.99, 20 5s
Gn 51N-2 Min Operate Time 0, 0.01 ... 19.99, 20 0s
Gn 51N-2 Follower DTL 0, 0.01 ... 19.99, 20 0s
Gn 51N-2 Reset (IEC/ANSI) Decaying, 0 ... 59, 60 0s
Gn 51N-2 VTS Action Off, Inhibit, Non-Dir Off
Gn 51N-2 Inrush Action Off, Inhibit Off
11.3 51N-3
Description Range Default
Gn 51N-3 Element Disabled, Enabled Disabled
Gn 51N-3 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 51N-3 Setting 0.05, 0.06 ... 2.49, 2.5 0.5xIn
Gn 51N-3 Char DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51N-3 Time Mult (IEC/ANSI) 0.025, 0.03 ... 99, 100 1
Gn 51N-3 Delay (DTL) 0, 0.01 ... 19.99, 20 5s