7SR18 Solkor Settings Guide
Unrestricted
© 2016 Siemens Protection Devices Limited Page 13 of 44
Description Range Default
Gn 51N-3 Min Operate Time 0, 0.01 ... 19.99, 20 0s
Gn 51N-3 Follower DTL 0, 0.01 ... 19.99, 20 0s
Gn 51N-3 Reset (IEC/ANSI) Decaying, 0 ... 59, 60 0s
Gn 51N-3 VTS Action Off, Inhibit, Non-Dir Off
Gn 51N-3 Inrush Action Off, Inhibit Off
11.4 51N-4
Description Range Default
Gn 51N-4 Element Disabled, Enabled Disabled
Gn 51N-4 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 51N-4 Setting 0.05, 0.06 ... 2.49, 2.5 0.5xIn
Gn 51N-4 Char DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51N-4 Time Mult (IEC/ANSI) 0.025, 0.03 ... 99, 100 1
Gn 51N-4 Delay (DTL) 0, 0.01 ... 19.99, 20 5s
Gn 51N-4 Min Operate Time 0, 0.01 ... 19.99, 20 0s
Gn 51N-4 Follower DTL 0, 0.01 ... 19.99, 20 0s
Gn 51N-4 Reset (IEC/ANSI) Decaying, 0 ... 59, 60 0s
Gn 51N-4 VTS Action Off, Inhibit, Non-Dir Off
Gn 51N-4 Inrush Action Off, Inhibit Off
11.5 50N-1
Description Range Default
Gn 50N-1 Element Disabled, Enabled Disabled
Gn 50N-1 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 50N-1 Setting 0.05, 0.06 ... 49.5, 50 0.5xIn
Gn 50N-1 Delay 0, 0.01 ... 14300, 14400 0s
Gn 50N-1 VTS Action Off, Inhibit, Non-Dir Off
Gn 50N-1 Inrush Action Off, Inhibit Off
11.6 50N-2
Description Range Default
Gn 50N-2 Element Disabled, Enabled Disabled
Gn 50N-2 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 50N-2 Setting 0.05, 0.06 ... 49.5, 50 0.5xIn
Gn 50N-2 Delay 0, 0.01 ... 14300, 14400 0s
Gn 50N-2 VTS Action Off, Inhibit, Non-Dir Off
Gn 50N-2 Inrush Action Off, Inhibit Off
11.7 50N-3
Description Range Default
Gn 50N-3 Element Disabled, Enabled Disabled
Gn 50N-3 Dir. Control Non-Dir, Forward, Reverse Non-Dir