7SR18 Solkor Settings Guide
Unrestricted
© 2016 Siemens Protection Devices Limited Page 43 of 44
Description Range Default
Gn CB Ph C Trip Count Disabled, Enabled Enabled
Gn CB Ph C Trip Count Target 0, 1 ... 9999, 10000 100
Gn CB E/F Trip Count Disabled, Enabled Enabled
Gn CB E/F Trip Count Target 0, 1 ... 9999, 10000 100
Gn CB Delta Trip Manual Open Disabled, Enabled Disabled
Gn CB Delta Trip Count Disabled, Enabled Disabled
Gn CB Delta Trip Count Target 0, 1 ... 9999, 10000 100
24.2 I^2T CB WEAR
Description Range Default
Gn I^2t Counter Disabled, Enabled Disabled
Gn Alarm Limit 10, 11 ... 99000, 100000 10MA^2s
Gn Separation Time 0, 0.001 ... 0.199, 0.2 0.02s
Gn Clearance Time 0, 0.001 ... 0.199, 0.2 0.04s
24.3 START COUNT
Description Range Default
Start Type(s) Combination of ( Power On,
Expected, Unexpected )
Power On,
Expected,
Unexpected
Start Count Target 0, 1 ... 9999, 10000 100
25 DATA STORAGE
25.1 DEMAND/DATA LOG
Description Range Default
Gn Demand Window 1, 2 ... 23, 24 24hrs
Gn Demand Window Type Fixed, Peak, Rolling Fixed
25.2 WAVEFORM STORAGE
Description Range Default
Gn P/F Trig Storage Combination of ( 51-1, 51-2, 51-3,
51-4, 50-1, 50-2, 50-3, 50-4 )
51-1, 51-2, 51-3,
51-4, 50-1, 50-2,
50-3, 50-4
Gn E/F Trig Storage Combination of ( 51N-1, 51N-2,
51N-3, 51N-4, 50N-1, 50N-2, 50N-
3, 50N-4, 51G-1, 51G-2, 51G-3,
51G-4, 50G-1, 50G-2, 50G-3,
50G-4 )
51N-1, 51N-2,
51N-3, 51N-4,
50N-1, 50N-2,
50N-3, 50N-4,
51G-1, 51G-2,
51G-3, 51G-4,
50G-1, 50G-2,
50G-3, 50G-4
Gn L/C Trig Storage Combination of ( 50-1LC, 50-2LC,
50G-1LC, 50G-2LC )
50-1LC, 50-2LC,
50G-1LC, 50G-
2LC
Gn Diff Current Storage Combination of ( 87L-1, 87L-2,
87HS-1, 87HS-2 )
87L-1, 87L-2,
87HS-1, 87HS-2

Table of Contents