7SR18 Solkor Settings Guide
Unrestricted
Page 44 of 44 © 2016 Siemens Protection Devices Limited
Description Range Default
Gn Misc Current Storage Combination of ( 46IT, 46DT, 37-1,
37-2, 37G-1, 37G-2, 49 Trip, 49
Alarm )
--------
Pre-trigger Storage 10, 20, 30, 40, 50, 60, 70, 80, 90 20%
Record Duration 10 Rec x 1 Sec, 5 Rec x 2 Sec, 2
Rec x 5 Sec, 1 Rec x 10 Sec
10 Rec x 1 Sec
25.3 FAULT STORAGE
Description Range Default
Gn Max Fault Rec Time 0, 1 ... 59900, 60000 2000ms
25.4 EVENT STORAGE
Description Range Default
Clear Events
Clear all stored event records
25.5 ENERGY STORAGE
Description Range Default
Gn Active Exp Energy Unit 1kWh, 10kWh, 100kWh, 1MWh,
10MWh, 100MWh
10kWh
Gn Active Imp Energy Unit 1kWh, 10kWh, 100kWh, 1MWh,
10MWh, 100MWh
10kWh
Gn Reactive Exp Energy Unit 1kVArh, 10kVArh, 100kVArh,
1MVArh, 10MVArh, 100MVArh
10kVArh
Gn Reactive Imp Energy Unit 1kVArh, 10kVArh, 100kVArh,
1MVArh, 10MVArh, 100MVArh
10kVArh
26 COMMUNICATIONS
Description Range Default
COM1-RS485 Protocol OFF, IEC60870-5-103, MODBUS-
RTU, DNP3
IEC60870-5-103
COM1-RS485 Station Address 0, 1 ... 65533, 65534 0
COM1-RS485 Baud Rate 75, 110, 150, 300, 600, 1200,
2400, 4800, 9600, 19200, 38400
19200
COM1-RS485 Parity NONE, ODD, EVEN EVEN
COM1-RS485 Mode Local, Remote, Local Or Remote Remote
LAN Protocol OFF, IEC60870-5-103 IEC60870-5-103
DNP3 Unsolicited Events Disabled, Enabled Disabled
DNP3 Destination Address 0, 1 ... 65533, 65534 0
DNP3 Application Timeout 5, 6 ... 299, 300 10s