7SR181 Solkor Technical Manual
Chapter 4 - Page 54 of 80 © 2016 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
618 LED 18 0,2 2 2
701 LED PU 1 0,2 2 2
702 LED PU 2 0,2 2 2
703 LED PU 3 0,2 2 2
704 LED PU 4 0,2 2 2
705 LED PU 5 0,2 2 2
706 LED PU 6 0,2 2 2
707 LED PU 7 0,2 2 2
708 LED PU 8 0,2 2 2
709 LED PU 9 0,2 2 2
710 LED PU 10 0,2 2 2
711 LED PU 11 0,2 2 2
712 LED PU 12 0,2 2 2
713 LED PU 13 0,2 2 2
714 LED PU 14 0,2 2 2
715 LED PU 15 0,2 2 2
716 LED PU 16 0,2 2 2
717 LED PU 17 0,2 2 2
718 LED PU 18 0,2 2 2
801 Binary Output 1 0,2 2 2
802 Binary Output 2 0,2 2 2
803 Binary Output 3 0,2 2 2
804 Binary Output 4 0,2 2 2
805 Binary Output 5 0,2 2 2
806 Binary Output 6 0,2 2 2
807 Binary Output 7 0,2 2 2
808 Binary Output 8 0,2 2 2
871 Cold Start 0,2 2 2
872 Warm Start 0,2 2 2
873 Re-Start 0,2 2 2
874 Power On 0,2 2 2
875 Expected Restart 0,2 2 2
876 Unexpected Restart 0,2 2 2
877 Reset Start Count 0,2 2 2
890 CB 1 Opened 0,2 2 2
891 CB 1 Closed 0,2 2 2
900 User SP Command 1 0,2 2 2
901 User SP Command 2 0,2 2 2
902 User SP Command 3 0,2 2 2
903 User SP Command 4 0,2 2 2
904 User SP Command 5 0,2 2 2
905 User SP Command 6 0,2 2 2