Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited Chapter 4 - Page 55 of 80
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
906 User SP Command 7 0,2 2 2
907 User SP Command 8 0,2 2 2
1063 CB DBI 0,2 2 2
1064 CB Travelling 0,2 2 2
1065 Close CB Failed 0,2 2 2
1066 Open CB Failed 0,2 2 2
1067 Start Count Alarm 0,2 2 2
1088 87L-1 0,2 2 2
1089 87L-2 0,2 2 2
1090 87HS-1 0,2 2 2
1091 87HS-2 0,2 2 2
1092 85S-1 0,2 2 2
1093 85S-2 0,2 2 2
1094 85S-3 0,2 2 2
1095 85S-4 0,2 2 2
1096 85S-5 0,2 2 2
1097 85S-6 0,2 2 2
1098 85R-1 0,2 2 2
1099 85R-2 0,2 2 2
1100 85R-3 0,2 2 2
1101 85R-4 0,2 2 2
1102 85R-5 0,2 2 2
1103 85R-6 0,2 2 2
1104 87R-1 0,2 2 2
1105 87R-2 0,2 2 2
1106 Protection Comms Alarm 0,2 2 2
1107 Protection Comms Test Mode 0,2 2 2
1108 79 Deadtime Inhibit 0,2 2 2
5.3.2 Double Bit Input Points
The default double bit input event buffer size is set to allow 100 events.
Double bit inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.