Examples
Various timed jobs (in 24 hour format):
1. "Job at 29th second of every minute"
(12:44:29, 12:45:29 etc.):
You must specify: Job type = 1 (Function no. in ACCU-2-L = 1)
Seconds = 29
2. "Job every hour at xx:14:15":
You must specify: Job type = 2 (Function no. in ACCU-2-L = 1)
Seconds = 15
Minutes = 14
3. "Job daily at 5:32:47":
You must specify: Job type = 3 (Function no. in ACCU-2-L = 1)
Seconds = 47
Minutes = 32
Format/hour = 85
4. "Job weekly, Tuesdays at 10:50:00":
You must specify: Job type = 4 (Function no. in ACCU-2-L = 1)
Seconds = 00
Minutes = 50
Format/hour = 90
Weekday = 01
5. "Job monthly, on the 14th at 7:30:15":
You must specify: Job type = 5 (Function no. in ACCU-2-L = 1)
Seconds = 15
Minutes = 30
Format/hour = 87
Day of month= 14
6. "Job yearly, on the 1st of May at 00:01:45":
You must specify: Job type = 6 (Function no. in ACCU-2-L = 1)
Seconds = 45
Minutes = 01
Format/hour = 80
Day of month= 01
Month = 05
Continued on the next page
OB 151: Set/Read Time for Clock-Controlled Interrupt
CPU 948 Programming Guide
6 - 48 C79000-G8576-C848-04

Table of Contents