EasyManua.ls Logo

Siemens CPU 948 - OB 124: Delete STEP 5 Blocks

Siemens CPU 948
548 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4 OB 124: Delete STEP 5 Blocks
Function
With OB 24, you can delete any STEP 5 blocks (logic and data
blocks) in the user memory. The deleted block is removed from the
address list in DB 0.
The gap in memory resulting from deleting a block is used again when
new blocks are loaded.
Parameters
1. ACCU-1-LH
Block type of the block to be deleted
2. ACCU-1-LL
Block number of the block to be deleted
Permitted block types and numbers:
ACCU-1-LH (block type) ACCU-1-LL (block number)
1 = PB
2 = SB
3 = FB
4 = FX
5 = DB
6 = DX
7 = OB
0 to 255
0 to 255
0 to 255
0 to 255
3 to 255
3 to 255
1 to 39
Result
After correct and error-free processing, the system program sets the
RLO to ’0’ and clears the condition codes CC 1 and CC 0.
Note
While the blocks are actually being deleted, user interrupts are
disabled: no interrupts come through.
By calling OB 124, the contents of ACCU 1 to ACCU 4 are
modified. The BR register is retained.
OB 124: Delete STEP 5 Blocks
CPU 948 Programming Guide
6 - 14 C79000-G8576-C848-04

Table of Contents

Related product manuals