4.3 START-UP Mode
The START-UP mode has the following features:
Mode change
START-UP is the transition from the STOP mode to the RUN mode.
Start-up types
The CPU 948 has the following start-up modes:
- COLD RESTART ( manual or automatic)
- WARM RESTART (manual or automatic)
(You can select the type of start-up with operating elements and by
assigning parameters in DX 0)
COLD RESTART
The cyclic user program is processed from the beginning.
The system program calls OB 20 as the user interface.
WARM RESTART
The execution of the cyclic user program is continued from the point
at which it was interrupted.
The system program calls the following OBs as the user interface:
- OB 21 for a MANUAL WARM RESTART,
- OB 22 for an AUTOMATIC WARM RESTART.
No time monitoring of the
start-up OBs
The execution time of the start-up organization blocks is not
monitored. You can call other blocks within these OBs. Make sure
you avoid endless loops!
Counters, timers, flags,
process images
The values of counters, timers, flags and process images are handled
differently in the various start-up types (refer to Section 4.4.3).
BASP
The BASP signal (disable output command) is active. This disables all
the digital outputs (exception: in the test mode in multiprocessor
operation, the BASP is not activated - refer to Section 10.1.8).
Interrupts
The interrupts (normal interrupts, process interrupts, timed interrupts)
are disabled.
Start-up in the multiprocessor
mode
Starting up in the multiprocessor mode is described in Section 10.1.7.
START-UP Mode
CPU 948 Programming Guide
4 - 16 C79000-G8576-C848-04

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 948 and is the answer not in the manual?

Siemens CPU 948 Specifications

General IconGeneral
BrandSiemens
ModelCPU 948
CategoryController
LanguageEnglish

Related product manuals