7.7 Use of Ethernet interfaces
Application
The following connections can be established via the Ethernet interfaces:
X120 provides the link to the system network (e.g. operator panels).
X130 connects the NCU to the company network.
X127 is used for commissioning and remote diagnostics via teleservice adapter IE.
You can 󹪝nd further details in the following manuals:
SINUMERIK 840D sl Basesoftware and Operating Software Commissioning Manual
SIMATIC TS Adapter IE Manual
Properties
The interfaces are full duplex 10/100/1000 Mbit Ethernet ports. Both ports are connected as an
Ethernet terminal.
Pin assignment
Table 7-9 Ethernet interfaces X120, X130, X127 in the 10/100 Mbit mode
Pin Signal name Signal type Meaning
1 TXP B Transmit data +
2 TXN B Transmit data -
3 RXP B Receive data +
4 - - Reserved, do not use
5 - - Reserved, do not use
6 RXN B Receive data -
7 - - Reserved, do not use
8 - - Reserved, do not use
Signal type: B = bidirectional
Table 7-10 Ethernet interfaces X120, X130, X127 in the 1 Gbit mode
Pin Signal name Signal type Meaning
1 DA+ B Bidirectional pair A+
2 DA- B Bidirectional pair A-
3 DB+ B Bidirectional pair B+
4 DC+ B Bidirectional pair C+
5 DC- B Bidirectional pair C-
6 DB- B Bidirectional pair B-
7 DD+ B Bidirectional pair D+
Connecting
7.7 Use of Ethernet interfaces
NCU 7x0.3B PN
58 Equipment Manual, 10/2020, 6FC5397-1EP40-6BA1

Table of Contents

Other manuals for Siemens MCP 398C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MCP 398C and is the answer not in the manual?

Siemens MCP 398C Specifications

General IconGeneral
BrandSiemens
ModelMCP 398C
CategoryControl Systems
LanguageEnglish

Related product manuals