Operation
Totalization 
The totalization function is based on the internal rate (mass per unit time) signal 
proportional to belt speed and load on the associated belt scale. It is not affected by the 
damping function (P080). The rate signal is sampled several times a second to accurately 
count the mass of material conveyed. The count is held in the master totalizer used to 
increment the internal totalizers and to produce a pulse signal for the remote totalizers. 
The BW100 provides four separate totalizer functions: 
• internal totalizer 1
• internal totalizer 2
• remote totalizer 1
• remote totalizer 2 
To avoid totalizing material at low flow rates, the totalizer drop out limit (P619) is set to a 
percentage of the design rate. Below this limit, totalization stops. When material flow 
returns to a rate above the drop out limit, totalization resumes. 
Totalizer resolution or count value is set by the respective control parameters, P631 --
P639. If the resolution selected causes the totalizer to lag behind the count rate, an E2 
error is displayed after making the parameter entry. The error is rectified by selecting a 
greater resolution value. 
Example: Internal totalizer 1 
Given: P005 = 1 (t/h)
P631 = 4
Then: totalizer count increments by 10 for each 10 metric tonnes registered 
External totalizer 1 
Given: P005 = 1 (t/h)
P638 = 5 
Then: contact closure occurs once for every 10 metric tonnes registered 
For remote totalization, the contact closure duration is set by the respective control 
parameters, P643 and P644. The value is automatically calculated upon entry of the 
design rate (P011) and remote totalizer parameters (P638 and P639), so that the duration 
of contact closure allows the relay response to track the total up to the design rate. The 
value can be changed to suit specific contact closure requirements, such as in the case 
of programmable logic controllers. If an E2 error is displayed, P638 or P639 has to be 
increased. 
The totalizers are reset through the master reset (P999), the totalizer reset (P648) or 
through the keypad. 
• master reset:  the reset of all totalizer functions is included in the master reset. 
• totalizer reset:  totalizer reset can be used to resets internal totalizers 1 and 2, or 
totalizer 2 independently. 
• keypad:  pressing  simultaneously while in the RUN mode resets 
internal totalizer 1, as well as the internal counts for both remote 
totalizers.