Parameters
Load Cell Balancing Parameters (P291 - P295) 
P291  Calculator Input 1 
This register displays the count associated with the summation of load cell A and B 
signals, when balancing the A and B load cells of the associated belt scale. 
P292 Calculator Input 2 
This register displays the count associated with the load B signal, when balancing the A 
and B load cells of the associated belt scale. 
P293 Calculator Input 3 
This register displays the count associated with the load cell B signal, when balancing 
the A and B load cells of the associated belt scale. 
P294 Calculator Input 4 
This register displays the count associated with the summation of load cell A and B 
signals, when balancing the A and B load cells of the associated belt scale. 
P295 Load Cell Balance 
Used in conjunction with balance calculator parameters (P291 - P 294), this parameter 
displays the adjustment required to complete the load cell balance procedure. 
End of balancing parameters 
P341 Run Time 
The cumulative days that the application device has been in service. The time is recorded 
once daily in a non-resetable counter. Periods of less than 24 hr. are not recorded, nor 
accumulated. 
Note: These parameters are used for verifying or balancing the load cells (2) on 
the associated conveyor belt scale. Refer to 
Start Up
, page 17, for details and 
procedure for use of these parameters.