Page 62 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
mmmmm
Parameters
Test and Diagnostic (P900 - P951)
P900 Software Revision
Displays the EPROM (Flash ROM) software revision level.
P901 Memory
Tests the memory. Test is initiated by scrolling to the parameter or repeated by pressing
ENTER.
Display:
PASS = normal
FAIL = consult Siemens Milltronics.
P907 Programmer Interface
Tests the infrared communications link. Test is initiated by scrolling to the parameter or
repeated by pressing ENTER.
Display:
PASS = normal
FAIL = consult Siemens Milltronics.
P911 mA Output Value
Displays the value from the previous measurement. A test value can be entered and the
displayed value is transmitted to the output. Upon returning to the RUN mode, the
parameter assumes the actual mA output level.
P940 Load Cell A, mV
in
Displays the mV signal input from the load cell. Range 0.00 - 60.00 mV.
Note: These parameters are used for test and diagnostic purposes.