Page 50 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
mmmmm
Communications
Parameters
P000 Security lock 
Locks out the programming change value function such that the values of P001 through 
P999 cannot be changed. This however does not prevent the select function from use; i.e. 
for viewing values. 
Programming is locked out if the value of P000 is other than 1954. 
Entry: 
1954 = unlocked
f
1954 = locked 
Quick Start (P005 to P017) 
P005  Design Rate Units 
Determines the units for programming and measurement.
Entry:
1
f
 
= t/hr (tonnes per hour)
2 = kg/hr (kilograms per hour)
3 = LT/Hr (long tons per hour)
4 = T/h (short tons per hour)
5 = lb/hr (pounds per hour)
Changing this parameter does not affect the rate (P011), belt speed (P014) or belt length 
(P016) parameters. These parameters should be re-entered for conformity in units. 
t = 1000 kg 
LT = 2240 lb. 
T = 2000 lb. 
P011 Design Rate 
Specifies the design rate of material flow for the belt scale. 
Enter the design rate from the supplied design data sheet 
Note: 
f
  denotes factory default.
Note: Quick Start is the minimum parameter programming required before 
attempting a calibration and successful entry into the RUN mode.