7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 51
mmmmm
Parameters
P014 Design Speed
Specifies the design speed for the conveyor belt.
Speed unit s are:
metre/s if P005 = 1 or 2
feet/min. if P005 = 3, 4 or 5
P015 Speed Constant
This value multiplied with the speed sensor frequency, calculates the actual belt speed.
Enter the speed constant = from the supplied design data sheet
or
= speed sensor pulses per revolution*
pulley circumference (m or ft)/ revolution
* refer to speed sensor nameplate or consult Siemens Milltronics or their agent.
P016 Belt Length
The length of the conveyor belt (one belt revolution).
Length units are:
metre if P005 = 1 or 2
feet if P005 = 3, 4 or 5
Enter the belt length
P017 Test Load
The load to be referenced when performing a span.
Load units are:
kg/m if P005 = 1 or 2
lb./ft. if P005 = 3, 4 or 5
The value for P017 can be calculated as follows:
Test Load=Total weight of of all test weights (kg) or (lb)
idler spacing (m) (ft)
End of Quick Start parameters. A calibration can now be performed.
Entry: If speed input is wired for constant speed (TB1 5/6 jumpered), value defaults to
100.
Note: Common speed sensor pulses per revolution:
RBSS - 150.4 pulses/meter (45.8 pulses/ft.)
TASS - 9.947 pulses/meter (3.03 pulses/ft.)