7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 53
mmmmm
Parameters
Relay/Alarm Function (P100 - P117)
P100 Relay Set Up
Sets the alarm mode for the relay.
Entry:
0 = off
1 = rate
2 = auto zero
3 = belt speed
4 = belt load
5 = error
P101 High Alarm
Sets the high alarm setpoint for relay functions P100 = 1, 3 or 4.
Enter the value in % of full scale.
P102 Low Alarm
Sets the low alarm setpoint for relay functions P100 = 1, 3 or 4.
Enter the value in % of full scale.
P117 Alarm Dead Band
Sets the dead band to prevent relay chatter due to fluctuations at the high or low
setpoint.
Enter the value in % of full scale
End of relay/alarm parameters.
mA Output Parameters (P200 - P220)
Note: These parameter are specific to the use of the relay/alarm function. Refer
to
Operation/Relay Output
, page 13.
Note: These parameters are specific to the use of the mA output. Refer to
Operation
on page 42 for details.