J-5
Appendix J
Trouble Message The Probable Cause Is:
MOI-1 Zone Disarmed Output of an MOI-7 (MOD-16 or VPM-5)
has been disarmed at the MXL.
More Than 60 Alarms The System alarm queue is full, and more
alarms have been received.
More Than 60 Securities The System security condition queue is
full, and more security conditions have
been received.
More Than 60 Supervisory The System supervisory queue is full, and
mor supervisories have been received.
More Than 60 Troubles The System trouble queue is full, and
more supervisories have ben received.
Multiple Module Response Two or more modules respond at the
same address.
Multiple Response Analog Poll Two or more analog devices at the same
address have reported during an analog
data request.
MXL Network Failure The MKB/RCC has lost communication
with the MNET.
Network CSGM Upload Needed A function was added to an XNET node
and had a reference to another node. This
function shall be added to each node it
references.
Network Input Disarmed A point on another XNET node has been
disarmed.
Network Loop A Failure The Style 7 primary (A) RS485 MNET
network loop has failed.
Network Loop B Failure The Style 7 secondary (B) RS485 MNET
network loop has failed.
No CSG - Default In Use No CSG-M custom programming was
found in FLASH memory so the system is
using the default CSG-M.
Node Disconnected XNET node was logically disconnected
from the NCC.
Node Multiple Response Two nodes are programmed at the same
address.