J-6
Appendix J
Trouble Message The Probable Cause Is:
Node Not Responding XNET wiring and/or NIM-1W module is
defective.
Out of RAM Call Support The configuration upload is too large.
Out of Tasks Call Support Contact the Siemens Industry, Inc. Techni-
cal Services Department.
Output Disarmed Indicates that an output point has been
manually disarmed.
PRE 1 Level AnaLASER device has reached its
pre-alarm setting.
Pre-alarm Device has reached its pre-alarm setting.
Pre-dirty Analog Volt. Reached IEC compensation has reached a level
where the detector should be cleaned.
Printer Off Line/Fault A supervised printer is not responding.
Printer Out Of Paper The printer has run out of paper.
Relay Coil Open The relay coil at this address is open.
Relay Disarmed The relay at this address has been dis-
armed from the Control menu.
Relay Driver Inoperative The relay on the CRM-4 or CSM-4 at this
address does not operate when com-
manded to energize.
Relay Supervision Failure The relay at this address has a coil failure.
ROM SW Version Error Module at the address noted needs an
update to latest available software level.
Signal Circuit Disarmed The NAC at this address was disarmed
from the Control panel.
Signal Circuit Loop Open The NAC at this address has a broken wire
or missing EOL device.
Signal Ckt Loop Shorted The NAC at this address is shorted, or the
EOL device is the wrong value, or the
notification appliances are not polarized or
are connected backwards.
PRE 2 Level