EasyManua.ls Logo

Siemens MXL-IQ - Page 151

Siemens MXL-IQ
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
J-7
Appendix J
Trouble Message The Probable Cause Is:
Signal Mod A/D Convert Fail The CSM-4 at this address has a failed
analog-to-digital converter.
Signal Module Zone Code Zone code failure on the CSM-4 module.
Software Key Violation Incorrect Software Key Installed (NCC
only).
Stack Fault Call Support When the message Call Support appears,
a four letter Alpha ID will be displayed. This
number is necessary when reporting the
problem to Siemens Industry, Inc.
Style 4 Network Mode The Style 4 jumper on a NET-7 is found on
a Style 7 system. Move the jumper to the
Style 7 position.
Style 7 Network Mode The Style 7 jumper on a NET-7 is found in
the Style 4 mode. Move the Style 7 jumper
to the Style 4 position.
System Commissioning Mode The system has been put in the commis-
sioning mode.
System Signal Power Failure A CSM-4 has lost power to its output
circuits.
Tamper Switch This is a security-type message for the
tamper switch on the SMB-2 board when
the system is selected for UL 1076 operation.
Too Many ALD-2s To many ALD-2Is are installed on the system.
This is beyond the maximum allowed.
Trouble Causing Input A device programmed on the system as
trouble causing has been activated and has
changed state.
Trouble Type Not Defined Unspecified trouble has been received from
this address.
Troubles Summarized While the system is in the commissioning
mode, the modules will display this message
in lieu of all the devices on this module.
Unspecified Dev Responding An analog device has reported at an
address not assigned in CSG-M.