J-8
Appendix J
Trouble Message The Probable Cause Is:
Unspecified Mod Responding A module has reported at an address not
assigned in CSG-M.
Unspecified Node Responding • NIM-1W address on another node is
incorrect.
• The network CSG-M is incorrect.
WALKTEST Activated The MXL-IQ has been placed in the walk
test mode.
Warm Reset The hardware reset input to the MXL-IQ
was used.
Watch Dog Circuit Triggered The watch dog circuit on the
SMB-2 triggered.
Zone Loop Open Broken wire on CZM-4 circuit.
Zone Loop Shorted Shorted wire on CZM-4 circuit.
Zone Power Loss The CZM-4 zone at this address has lost its
24 volt input.