New Two Stage Alarm
For use in Canada only with MXL-IQ software version 1.0 and higher
Canadian Two Stage Alarm is available
with revision 1.0 of MXL-IQ firmware and
revision 6.07 of CSG-M. All new installations
of Two Stage Alarm should use the new
implementation.
The hardware requirements for the Two
Stage Alarm are as follows:
• MXL-IQ firmware revision 1.0 or higher
• CSG-M revision 6.07 or higher
• CSM-4s must contain revision 4 or
higher
The new Two Stage implementation is
designed for flexibility. It allows the system
designer/programmer to define how Two
Stage alarm should function.
Selecting Two Stage
A new selection in the CSG-M determines
which version of Two Stage Alarm is used
in an MXL-IQ. In the Other System Flags
menu (under the Options, System Mes-
sage, Authorizations menu), a YES/NO
option has been added for New Two Stage
Configuration. This flag determines which
implementation of Two Stage alarm is used
in the MXL-IQ.
Fire Protection Company Name
CSG-M Memory=2864 used, 243212 free CONFIG => TWOSTG
Other System Flags
Sensitivity Adjustments Allowed -----------------> NO
Block Alarm and Trouble Acknowledge Allowed -----> YES
Multienclosure System ---------------------------> NO
Device disarm through RESET ---------------------> NO
Self restoring troubles -------------------------> NO
NFPA 71 connection ------------------------------> NO
NET 7 panel checking ----------------------------> NO
Network Repeater Used ---------------------------> NO
Independent Function Keys -----------------------> NO
New Two Stage Configuration ---------------------> YES
Move Cursor to Select, ENTER to TOGGLE ESC = Prev. Menu
CSG-M Other System Flags Menu