Chapter 6
Certification
RUGGEDCOM RX1400
Installation Guide
50 EMC and Environmental Type Tests
Test Description Test Levels
Severity
Levels
± 2 kV Line-to-Line
DC Power Ports ± 2 kV Line-to-Earth
± 1 kV Line-to-Line
3
AC Power Ports ± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Conducted) RFI
Earth Ground Ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure Ports 100 A/m Continuous
1000 A/m for 1 s
5
IEC 61000-4-9 Pulse Magnetic Field Enclosure Ports 300 A/m 4
IEC 61000-4-11 Voltage Dips & Interrupts AC Power Ports 30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
Signal PortsIEC 61000-4-16 Mains Frequency Voltage
DC Power Ports
30 V Continuous
300 V for 1s
4
IEC 61000-4-17 Ripple on DC Power Supply DC Power Ports 10% 3
IEC 61000-4-18 Damped Oscillatory Wave Slow Damped 2.5 kV Common
100 kHz or 1 MHz
3
IEC 61000-4-29 Voltage Dips and Interrupts DC Power Ports 30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports
DC Power Ports
Dielectric Strength
AC Power Ports
2 kV
Signal Ports
IEC 60255-5
HV Impulse
DC Power Ports
5 kV
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RX1400 meets Class 1 requirements for copper ports, which allows for temporary
communication loss.
Test Description Test Levels
IEEE 1613 HV Impulse Signal Ports 5 kV

Table of Contents

Other manuals for Siemens RUGGEDCOM RX1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RX1400 and is the answer not in the manual?

Siemens RUGGEDCOM RX1400 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RX1400
CategoryNetwork Hardware
LanguageEnglish

Related product manuals