Basic instructions
7.8 Program control operations
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
265
Structure components
Data type
Description
DB_NUMBER
UInt
(D) Number of the data block
OFFSET
UDInt
(E) Relative address of the operand
GET_ERROR_ID
Table 7- 110 GetErrorID instruction
LAD / FBD
SCL
Description
GET_ERR_ID();
Indicates that a program block execution error has occurred and reports
the ID (identifier code) of the error.
Table 7- 111 Data types for the parameters
Parameter
Data type
Description
ID
Word
Error identifier values for the ErrorStruct ERROR_ID member
Table 7- 112 Error_ID values
ERROR_ID
hexadecimal
ERROR_ID decimal
Program block execution error
0
0
No error
2520
9504
Corrupted string
2522
9506
Operand out of range read error
2523
9507
Operand out of range write error
2524
9508
Invalid area read error
2525 9509 Invalid area write error
2528
9512
Data alignment read error (incorrect bit alignment)
2529
9513
Data alignment write error (incorrect bit alignment)
252C
9516
Uninitialized pointer error
2530
9520
DB write protected
253A
9530
Global DB does not exist
253C
9532
Wrong version or FC does not exist
253D
9533
Instruction does not exist
253E
9534
Wrong version or FB does not exist
253F
9535
Instruction does not exist
2575
9589
Program nesting depth error
2576
9590
Local data allocation error
2942
10562
Physical input point does not exist
2943
10563
Physical output point does not exist