Technical specifications
A.14 Communication interfaces
S7-1200 Programmable controller
976 System Manual, 03/2014, A5E02486680-AG
Table A- 251 Power supply
Table A- 252 RS232 connector (male)
Data carrier detect: Input
Received data from DCE: Input
Transmitted data to DCE: Output
Data terminal ready: Output
Ring indicator (not used)
5 GND Logic ground SHELL Chassis ground
CM 1241 RS422/485 specifications
CM 1241 RS422/485 Specifications
Table A- 253 General specifications
Dimensions W x H x H (mm)
Table A- 254 Transmitter and receiver
RS422 or RS485, 9-pin sub D female connector
Common mode voltage range
-7 V to +12 V, 1 second, 3 VRMS continuous
Transmitter differential output voltage 2 V min. at R
L
= 100 Ω
1.5 V min. at R
L
= 54 Ω
Termination and bias 10K Ω to +5 V on B, PROFIBUS Pin 3
10K Ω to GND on A, PROFIBUS Pin 8
Internal bias options provided, or no internal bias. In all cases,
external termination is required, see Biasing and terminating an
RS485 network connector (Page 670) and Configuring the RS422
and RS485 in the S7-1200 System Manual (Page 707)
5.4K Ω min. including termination
Receiver threshold/sensitivity
+/- 0.2 V min., 60 mV typical hysteresis