S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
783
Online and diagnostic tools
14
14.1
Status LEDs
The CPU and the I/O modules use LEDs to provide information about either the operational
status of the module or the I/O.
Status LEDs on a CPU
The CPU provides the following status indicators:
STOP/RUN
Solid yellow indicates STOP mode
Solid green indicates RUN mode
Flashing (alternating green and yellow) indicates that the CPU is in STARTUP mode
ERROR
Flashing red indicates an error, such as an internal error in the CPU, a error with the
memory card, or a configuration error (mismatched modules)
Defective state:
- Solid red indicates defective hardware
- All LEDs flash if the defect is detected in the firmware
MAINT (Maintenance) flashes whenever you insert a memory card. The CPU then
changes to STOP mode. After the CPU has changed to STOP mode, perform one of the
following functions to initiate the evaluation of the memory card:
Change the CPU to RUN mode
Perform a memory reset (MRES)
Power-cycle the CPU
You can also use the LED instruction (Page 346) to determine the status of the LEDs.
Table 14- 1 Status LEDs for a CPU
Description
STOP/RUN
Yellow / Green
ERROR
Red
MAINT
Yellow
Power is off
Off
Off
Off
Startup, self-test, or firmware
update
Flashing
(alternating yellow and green)
- Off
Stop mode
On (yellow)
-
-
Run mode
On (green)
-
-
Remove the memory card
On (yellow)
-
Flashing
Error
On (either yellow or green)
Flashing
-