SM 1278 4xIO-Link Master
15.4 Interrupt, error, and system alarms
S7-1200 Programmable controller
826 System Manual, 03/2014, A5E02486680-AG
No error
Error
Module errors are indicated as diagnostics (module status) only in IO-Link mode.
Meaning (IO-Link error code)
Short-circuit 1
Short-circuit at the process cables on the IO-Link device
Short-circuit on IO device
Undervoltage 2 5111
Supply voltage too low X
Overheating 5
Temperature exceeded on master
4000
Temperature exceeded on device X
Wire break 6 1800
• No IO-Link device connected
• There is a break on the signal line to the IO-Link device
• IO-Link device cannot communicate due to a different error
X
Overflow 7 8C10
Process tag range exceeded X
Process tag range too low
Error 9 --- All IO-Link error codes that are not listed here are mapped to
X
Parameter
assignment
error
16 1882
IO-Link master could not be configured X
1802 Incorrect device
6320
6321
Device was not configured correctly X
Supply
voltage
17
L+ supply voltage for device missing
X
1807 L+ supply voltage for device too low (<20 V)