Communication processor and Modbus TCP
12.3 Point-to-point (PtP) communication
S7-1200 Programmable controller
680 System Manual, 03/2014, A5E02486680-AG
Parameter
Definition
Recognize message end by
message timeout
The message end occurs when the configured amount of time to wait for the message end
has expired. The message timeout period begins when a start condition has been satisfied.
The default is 200 ms and the range is 0 to 65535 ms.
Received characters
Start Message condition satisfied: message timer starts
Message timer expires and terminates the message
Recognize message end by
response timeout
The message end occurs when the configured amount of time to wait for a response
expires before a valid start sequence is received. The response timeout period begins
when a transmission ends and the CM or CB begins the receive operation. The default
response timeout is 200 ms and the range is 0 to 65535 ms. If a character is not received
within the response time period, RCVTIME, then an error is returned to the corresponding
RCV_PTP instruction. The response timeout does not define a specific end condition. It
only specifies that a character must be successfully received within the specified time. You
must configure another end condition to indicate the actual end of a message.
Transmitted characters
Received characters
First character must be successfully received by this time.