Communication processor and Modbus TCP
12.3 Point-to-point (PtP) communication
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
691
SEQ[1].CTL IN Byte Sequence 1 ignore/compare control for each character: (Default
value: B#16#0)
These are the enabling bits for each character in start sequence
• 01H - Character 1
• 02H - Character 2
• 04H - Character 3
• 08H - Character 4
• 10H - Character 5
Disabling the bit associated with a character means any character
will match, in this sequence position.
Sequence 1 start characters (5 characters). Default value: 0
SEQ[2].CTL IN Byte Sequence 2 ignore/compare control for each character. Default
Sequence 2 start characters (5 characters). Default value: 0
SEQ[3].CTL IN Byte Sequence 3 ignore/compare control for each character. Default
Sequence 3 start characters (5 characters). Default value: 0
SEQ[4].CTL IN Byte Sequence 4 ignore/compare control for each character. Default
Sequence 4 start characters (5 characters), Default value: 0
Consider the following received hexadecimal coded message: "
10 aa
bb 10 aa 16"
and the configured start sequences shown in the table below. Start sequences begin to be
evaluated when the first 68H character is successfully received. Upon successfully receiving
the fourth character (the second 68H), then start condition 1 is satisfied. Once the start
conditions are satisfied, the evaluation of the end conditions begins.
The start sequence processing can be terminated due to various parity, framing, or inter-
character timing errors. These errors result in no received message, because the start
condition was not satisfied.
Table 12- 16 Start conditions
3 dcH aaH xx xx xx