Communication processor and Modbus TCP
12.3 Point-to-point (PtP) communication
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
709
Configuring the RS485
For RS485 mode, there is only one operating mode. The different selections for Receive line
initial state reference the cases shown below for more details.
Half duplex (RS485) two wire mode. In the Receive line initial state:
Select none when you supply the bias and termination (Case 5).
Select forward bias to use internal bias and termination (Case 4).
Case 4: RS485: Forward bias
Mode of operation: RS485
Receive line initial state: Forward bias (biased with R(B) > R(A) > 0 V)