EasyManua.ls Logo

Siemens S7-1200 - Page 896

Siemens S7-1200
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.7 Digital signal modules (SMs)
S7-1200 Programmable controller
896 System Manual, 03/2014, A5E02486680-AG
Table A- 114 Digital outputs
Model
SM1222
DQ 16 x Relay
SM1222
DQ 16 x 24 VDC
Number of outputs 16 16
Type
Relay, dry contact
Solid state - MOSFET (sourcing)
Voltage range
5 to 30 VDC or 5 to 250 VAC
20.4 to 28.8 VDC
Logic 1 signal at max. current
-
20 VDC min.
Logic 0 signal with 10K Ω load
-
0.1 VDC max.
Current (max.)
2.0 A
0.5 A
Lamp load
30 W DC/200 W AC
5 W
ON state contact resistance
0.2 Ω max. when new
0.6 Ω max.
Leakage current per point
--
10 μA max.
Surge current
7 A with contacts closed
8 A for 100 ms max.
Overload protection
No
No
Isolation (field side to logic) 1500 VAC for 1 minute (coil to
contact)
None (coil to logic)
500 VAC for 1 minute
Isolation resistance
100 MΩ min. when new
-
Isolation between open contacts
750 VAC for 1 minute
-
Isolation groups
4
1
Current per common (max.)
10 A
8 A
Inductive clamp voltage
-
L+ minus 48 V, 1 W dissipation
Switching delay 10 ms max. 50 μs max. off to on
200 μs max. on to off
Maximum relay switching frequency
1 Hz
-
Lifetime mechanical (no load)
10,000,000 open/close cycles
-
Lifetime contacts at rated load (N.O.
contact)
100,000 open/close cycles -
Behavior on RUN to STOP Last value or substitute value (default
value 0)
Last value or substitute value (default
value 0)
Number of outputs on simultaneously
8 (no adjacent points) at 60 °C
horizontal or 50 °C vertical
16 at 55 °C horizontal or 45 °C
vertical
16
Cable length (meters)
500 m shielded, 150 m unshielded
500 m shielded, 150 m unshielded

Table of Contents