Appendix
A.1 Modbus TCP
118 Equipment Manual, 09/2022, L1V30415168B-03
Reading out the profile data memory (load profile, daily profile, monthly profile, annual
profile)
Each of the profile data memories contains 2 measuring channels:
• Measuring channel 1: Active energy or active power import
• Measuring channel 2: Active energy or active power export
A special feature of the load profile memory (demand period duration of 15 minutes) is that
these channels are also available as
• Arithmetic average power demand values (W)
• Cumulated average power demand values (W) and/or as
• Energy portions (Wh)
Each of these values can be converted to any of the others using the demand period duration
and the real measurement duration which is also available.
Any entry in the profile data memory can be marked as a data variable ("information flag
bytes") by the device. This information helps the user to identify occurrences during the
demand periods.
Description of the "information flag bytes":
FLAG_QUALITY_AUXPOWER_FAIL
FLAG_QUALITY_PERIOD_TO_SHORT
FLAG_QUALITY_TIME_UNSECURE
Examples
A number of Modbus frames are provided here to indicate the readout of various data logs in
the device using the function code 0x64.
Example of request frame
(Tagesprofilspeicher)
channels energy)
identifiers (4 byte OID
and 1 byte number of
0x0000 0x0000
0x0009 0x01