Appendix
A.1 Modbus TCP
90 Equipment Manual, 09/2022, L1V30415168B-03
A.1.2 Modubs exception codes
Overview
Table A- 2 Modubs exception codes
Exception codes
Name
Meaning
Remedy
01
Illegal
Function
Illegal function:
The function code in the
request is not a permissible
action for the slave.
The slave is in a status in which
it cannot process a request of
this type. This is the case, for
example, if it has not yet been
configured and is requested to
return register values.
Check which function
codes are supported.
02
Illegal Data
Address
Illegal data address
This address is not permissible for
the slave. This is the case, for
example, if the combination of start
offset and transfer length is invalid.
Check the offset and the
number of registers.
03
Illegal Data
Value
Illegal data value:
The request contains a data value
that is not permissible for the slave.
This indicates an error in the
remaining structure of a complex
request, e.g. an incorrect data
length.
Check that the specified
offset and the specified
data length in the
command are correct.
04
Slave Device
Failure
Error in processing the data:
An indefinite error occurred when
the slave attempted to execute the
requested action.
Check that the specified
offset and the specified
data length are correct.
F0
Write
Protection ON
The action has been rejected
because the write protection is set.
Deactivate write
protection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SENTRON PAC3200T and is the answer not in the manual?

Siemens SENTRON PAC3200T Specifications

General IconGeneral
BrandSiemens
ModelSENTRON PAC3200T
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals