Appendix
A.1 Modbus TCP
Equipment Manual, 09/2022, L1V30415168B-03
127
A.1.11 Modbus communication parameters with the function codes 0x03, 0x04
and 0x10
Addressing the communication parameters
Table A- 13 Communication parameters
Offset Number of
registers
Name Unit Format
Applicable
Modbus
function
codes
Value range Access
62997
2
IP filter
ON/OFF
unsigned long
0x03
0x04
0x10
RW
63001
2
IP address
unsigned long
0x03
0x04
0x10
0 ... FFFFFFFFh
RW
63003
2
Subnet mask
unsigned long
0x03
0x04
0x10
0 ... FFFFFFFFh
RW
63005
2
Gateway
unsigned long
0x03
0x04
0x10
0 ... FFFFFFFFh
RW
63007
2
Bootloader Version
unsigned long
0x03
0x04
char, uchar, uchar,
uchar
R
63009
2
Password Protection
ON/OFF
unsigned long
0x03
0x04
0; 1
R
64001
27
IM0 data
IM0STRUCT
0x03
0x04
R
64028
89
IM1 IM4 data
IM14STRUCT
0x03
0x04
0x10
RW