Appendix
A.1 Modbus TCP
Equipment Manual, 09/2022, L1V30415168B-03
125
Table A- 10 Settings parameters for the universal counter source
Offset
Number of
registers
Name Unit Format Value range Access
50051
2
Universal counter
source
Unsigned long
0 =
Digital input
RW
1 =
Digital output
2 =
Limit logic
3 =
Limit 0
4 =
Limit 1
5 =
Limit 2
6 =
Limit 3
7 =
Limit 4
8 =
Limit 5
Table A- 11 Setting parameter for limit 0
Offset
Number of
registers
Name Unit Format Value range Access
50063
2
ON/OFF
Unsigned long
0 =
OFF
RW
1 =
ON
50065
2
Hysteresis
%
Float
0.0 ... 20.0
RW
50067
2
Delay
s
Unsigned long
0 ... 10
RW
50069
2
Operation in Limit
Logic
Unsigned long
0 =
Not used
RW
1 =
AND
2 =
OR
50071
2
Source
Unsigned long
0 =
V_L1
RW
1 =
V_L2
2 =
V_L3
3 =
V_L12
4 =
V_L23
5 =
V_L31
6 =
I_L1
7 =
I_L2
8 =
I_L3
9 =
VA_L1
10 =
VA_L2
11 =
VA_L3
12 =
P_L1
13 =
P_L2
14 =
P_L3
15 =
VARQ1_L1
16 =
VARQ1_L2
17 =
VARQ1_L3
18 =
PF_L1
19 =
PF_L2
20 =
PF_L3
21 =
THDV_L1
22 =
THDV_L2

Table of Contents