Commissioning
6.3 Parameterizing the device
Equipment Manual, 09/2022, L1V30415168B-03
65
"Result Logic Array" parameter
The device can be used to monitor the violation of up to 6 limit values. If a limit value is
violated, specific actions can be triggered. In addition, the limit values can be combined with
each other using a logic operation. The result of the logic operation can also be used to
trigger specific actions.
Selection Range Factory
Possibility of logic operations on limit values. Logic operations
are always performed on the limit values according to the
following formula:
(((((op0 LIM0 op1 LIM1) op2 LIM2) op3 LIM3) op4 LIM4) op5
LIM5) = RLO
• LIM0: Limit 0
• LIM1: Limit 1
• LIMx Limit x
• op: Logic operator AND / OR / ----
"----": Limit value is not combined with any other limit value.
The result of the logic operation is the "LIMIT LOGIC".
synchronizatio