Technical data
8.1 Technical data
78 Equipment Manual, 09/2022, L1V30415168B-03
Measuring inputs for voltage
Measuring inputs
Voltage U
n L-N / L-L
100 V / 173 V AC, 50 / 60 Hz
230 V / 400 V AC, 50 / 60 Hz
Max. measurable voltage
Voltage L-N
230 V 3AC (+20%)
Voltage L-L
400 V 3AC (+20%)
Min. measurable voltage
Voltage L-N
100 V 3AC (-80%)
Voltage L-L
173 V 3AC (-80%)
Zero point suppression level
Voltage L-N
7 V
Voltage L-L
10 V
Impulse withstand voltage
6.5 kV (1.2 / 50 µs)
Measuring category
CAT III (acc. to IEC 61010-2-030)
Input resistance (L-N)
1
Measuring inputs for current
Only for connection to AC power systems via external current transformers.
Measuring inputs
Input current II
1 A / 5 A
Max. permissible continuous current
10 A
Current impulse overload capability
100 A for 1 s
Zero point suppression level
1 mA / 5 mA
Max. power consumption per phase
300 mA at 5 A
Measuring range
1 ... 120%