Technical data
8.1 Technical data
80 Equipment Manual, 09/2022, L1V30415168B-03
Digital output
Digital output
Number
1
Type
Passive
Design/function
Switching output or pulse output
Maximum switching voltage
30 V
Output current
For signal "1"
Depends on the load and the external power
supply
Continuous load
≤50 mA (thermal overload protection)
Transient overload
≤130 mA for 100 ms
For signal "0"
≤0.2 mA
Internal resistance
30 Ω
Overvoltage category
CAT I
Pulse output function
Standard for pulse emitter
Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration
30500 ms
Min. settable time frame
10 ms
Max. switching frequency
17 Hz
Short-circuit protection
Yes
Communication
Ethernet interface
Ethernet
Modbus TCP; web server (HTTP); SNTP; DHCP
Ethernet connection
RJ-45
Data rate
10/100 Mbps
Autocrossover
Available
Autonegation
Available
Connection elements
Power connection: IL1, IL2, IL3
mm
2
AWG
Conductor cross-section for copper cable (Cu)
Rigid
1 x 0.2 ... 6.0
1 x 24 ... 10
Flexible
1 x 0.2 ... 4.0
1 x 24 ... 12
Flexible with end sleeve, without plastic
sleeve
1 x 0.2 ... 4.0
1 x 24 ... 12
Flexible with end sleeve and plastic
sleeve
1 x 0.25 ... 4.0
1 x 24 ... 12
Tightening torque
0.5 ... 0.6 Nm
[4.4 ... 5.3 lb-in]

Table of Contents