Technical data
8.1 Technical data
82 Equipment Manual, 09/2022, L1V30415168B-03
Degree of protection and protection class
Degree of protection and protection class
Protection class
Safety class II
Degree of protection according to IEC 60529
Front area
IP40
Termination area
IP20
If higher degree of protection requirements are placed on the application engineering, the
customer must take suitable measures. This includes installation in a protective enclosure
with degree of protection IP51 or higher.
Environmental conditions
Operation is only permissible inside an enclosed dry room.
Environmental conditions
Temperature range
Ambient temperature during operating
phase
-25 °C … +55 °C /
-40 °C ... +70 °C
(depending on HW, see device)
Ambient temperature during transport
and storage
-40 °C ... +70 °C
Relative humidity
< 75 % RH
Installation altitude above sea level
max. 2000 m
Device mounting position
Any
Degree of pollution
2
Environmental tests
EN 60068-2-6
EN 60068-2-27
EN 60068-3-3
Electromagnetic environment
interference emission
EN 61326-1
EN 61000-3-2 (harmonic currents)
EN 61000-3-3 (voltage variations and flicker)
Limit values complied with for emitted
interference
Class B, used in the household sector
Interference immunity
EN 61326-1
(use in an industrial environment)
Standards considered for immunity
EN 61000-4-2 (electrostatic discharge)
EN 61000-4-3 (electromagnetic RF fields)
EN 61000-4-4 (rapid transients - burst)
EN 61000-4-5 (surge voltages - surge)
EN 61000-4-6 (conducted RF fields)
EN 61000-4-8 (magnetic fields)
EN 61000-4-11 (voltage dips)