Format 16-bit unsigned integer
Range 25 to 150
Unit A
Default 60
I
1
Power-Flow Direction
(Address 56) This register defines the I
1
power-flow direction parameter.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 1
0 = Not reversed
1 = Reversed
Unit
Default 0 = Not reversed
I
2
/I
N
Power-Flow Direction
(Address 57) This register defines the I
2
/I
N
power-flow direction parameter.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 1
0 = Not reversed
1 = Reversed
Unit
Default 1 = Reversed
I
3
Power-Flow Direction
(Address 58) This register defines the I
3
power-flow direction parameter.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 1
0 = Not reversed
1 = Reversed
Unit
Modbus Registers
B.4 Register-Type Data – Holding Registers
124 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019