EasyManua.ls Logo

Siemens SICAM - Page 155

Siemens SICAM
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reactive Power Q2 for Phase 2
(Address, see Table B-16) This register contains the minimum values and the maximum values of the reactive
power for phase 2 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to Reactive Power Q1 for Phase 1, Page 154.
Reactive Power Q3 for Phase 3
(Address, see Table B-16) This register contains the minimum values and the maximum values of the reactive
power for phase 3 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to Reactive Power Q1 for Phase 1, Page 154.
Apparent Power S1 for Phase 1
(Address, see Table B-16) This register contains the minimum values and the maximum values of the apparent
power for phase 1 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit 1/10 kVA for 230-V sensor
1 kVA for 3.25/√3 sensor, for 100/√3 sensor, and for 400/√3 sensor
Range 0 to 65535
Apparent Power S2 for Phase 2
(Address, see Table B-16) This register contains the minimum values and the maximum values of the apparent
power for phase 2 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to Apparent Power S1 for Phase 1, Page 155.
Apparent Power S3 for Phase 3
(Address, see Table B-16) This register contains the minimum values and the maximum values of the apparent
power for phase 3 measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to Apparent Power S1 for Phase 1, Page 155.
Modbus Registers
B.8 Register-Type Data – Trailing Pointers
SICAM, Feeder Condition Monitor, Manual 155
E50417-H8940-C580-A4, Edition 03.2019

Table of Contents

Related product manuals