▶ CROSSBLOCK
TIMER
▶ 0 ms to 60 000 ms
▶ OK
▶ TIMER LOGIC ▶ TIMER LOGIC T1 ▶ 0 to 60 s
(Enhanced fault validation and reset function
is disabled)
▶ SAVE
▶ TIMER LOGIC T2 ▶ 0 to 25 s
(Enhanced fault validation and reset function
is disabled)
▶ SAVE
▶ TIMER LOGIC T2 ▶ 0 to 240 s
(Enhanced fault validation and reset function
is disabled)
▶ SAVE
Table A-5 Parameters Menu Structure - Timer Logic and Process Parameters
PROCESS
PARAMETERS
▶ CORRECTION
FACTOR
▶ DISABLE (Default)
▶ ENABLE
▶ VOLTAGE
PARAMETERS
▶ LV TO MV CALCU-
LATION
▶ TRANSFORMER
TYPE
▶ DY-11
▶ TRANSFORMER
ANGLE
▶ 0° to 359°
▶ SAVE
▶ PRIMARY
VOLTAGE
CORRECTION
▶ 0 V to 900 V
▶ SAVE
▶ CAPACITIVE
VOLTAGE MEAS-
UREMENT
▶ AUTO CALIBRA-
TION VOLTAGE
▶ 1000 V to 36000 V
▶ SAVE
▶ AUTO CALIBRA-
TION
▶ START AUTO CALI-
BRATION
▶ OK
▶ RATED SEC.
VOLTAGE
▶ AC 3.25/√3 or AC 100/√3 V or AC 230 V or
AC 400/√3
▶ SAVE
▶ RATED PRI.
VOLTAGE
▶ 1.0 kV to 36.0 kV
▶ SAVE
▶ SENSOR VOLTAGE
PRIMARY
▶ 1.0 kV to 36.0 kV
▶ SAVE
▶ VOLTAGE CORREC-
TION FACTOR
▶ V
1
MAGNITUDE
FACTOR
▶ V
1
ANGLE OFFSET
▶ V
2
MAGNITUDE
FACTOR
▶ V
2
ANGLE OFFSET
Parameterization
A.2 Parameterizing the User Interface
88 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019