▶ PULSETH OP. ▶ 0 to 100
(Set to "0" to disable the
detection function)
▶ SAVE
▶ PULSETH MON. ▶ 0 to 100
(Set to "0" to disable the
detection function)
▶ SAVE
▶ INTERMIT-
TENT
GROUND
FAULT
▶ NOS. DET. ▶ 0 to 999
(Set to "0" to disable the
detection function)
▶ SAVE
▶ T-DET.EXT ▶ 0 to 600
(Set to "0" to disable the
detection function)
▶ SAVE
Table A-4 Parameters Menu Structure - Fault Parameters
FAULT
PARAME-
TERS
▶ OVERVOLTAGE
ALERTS
▶ OVERVOLTAGE
WARNING
▶ 0 % to 30 %
(Set to "0" to disable the overvoltage
warning)
▶ SAVE
▶ OVERVOLTAGE
ALARM
▶ 0 % to 30 %
(Set to "0" to disable the overvoltage alarm)
▶ SAVE
▶ UNDER-
VOLTAGE
ALERTS
▶ UNDER-
VOLTAGE
WARNING
▶ 0 % to 30 %
(Set to "0" to disable the undervoltage
warning)
▶ SAVE
▶ UNDER-
VOLTAGE
ALARM
▶ 0 % to 30 %
(Set to "0" to disable the undervoltage alarm)
▶ SAVE
▶ OVERCURRENT
ALERTS
▶ OVERCURRENT
WARNING
▶ 50 A to 2000 A
(Set to "0" to disable the detection function)
▶ SAVE
▶ OVERCURRENT
ALARM
▶ 50 A to 2000 A
(Set to "0" to disable the detection function)
▶ SAVE
▶ OVERCURRENT
TWARNING
▶ 1 min to 120 min
(Set to "0" to disable the overcurrent
warning)
▶ SAVE
▶ OVERCURRENT
TALARM
▶ 1 min to 120 min
(Set to "0" to disable the overcurrent alarm)
▶ SAVE
▶ AUTO RESET
TIME
▶ 0 min to 480 min
(Set to "0", auto reset is immediate on fault restoration)
▶ SAVE
Parameterization
A.2 Parameterizing the User Interface
SICAM, Feeder Condition Monitor, Manual 87
E50417-H8940-C580-A4, Edition 03.2019