TIME SETTING
tV
NG
>
0.04 s to 60 s
SAVE
I
dir
0.2 A to 30 A
(Set to "0" to disable the
cos ϕ/sin ϕ method)
SAVE
NEUTRAL-POINT
TREATMENT
SOLID or ISOLATED or RESO-
NANT
SAVE
GROUP2
SETTING
GROUND-FAULT
DETECTION I
N
>
0.4 A to 2000 A
(Set to "0" to disable the
detection function)
SAVE
GROUND-FAULT
DETECTION tI
N
>
0.04 s to 60 s
SAVE
THRESHOLD
SETTING V
NG
>
0 % to 100 %
(Set to "0", the ground-fault
detection is based on I
N
>)
SAVE
TIME SETTING
tV
NG
>
0.04 s to 60 s
SAVE
I
dir
0.2 A to 30 A
(Set to "0" to disable the
cos ϕ/sin ϕ method)
SAVE
NEUTRAL-POINT
TREATMENT
SOLID or ISOLATED or RESO-
NANT
SAVE
V< 0 % to 100 %
(Set to "0" to disable the detection function)
SAVE
V> 0 % to 170 %
(Set to "0" to disable the detection function)
SAVE
PULSE
DETEC-
TION
3I0 DELTA 0 % to 300 %
(Set to "0" to disable the
detection function)
SAVE
PULSE
DETEC-
TION
TPULSE ON 0.50 s to 20 s
(Set to "0" to disable the
detection function)
SAVE
TPULSE OFF 0.50 s to 20 s
(Set to "0" to disable the
detection function)
SAVE
Parameterization
A.2 Parameterizing the User Interface
86 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019