▶ TIME SETTING
tV
NG
>
▶ 0.04 s to 60 s
▶ SAVE
▶ I
dir
▶ 0.2 A to 30 A
(Set to "0" to disable the
cos ϕ/sin ϕ method)
▶ SAVE
▶ NEUTRAL-POINT
TREATMENT
▶ SOLID or ISOLATED or RESO-
NANT
▶ SAVE
▶ GROUP2
SETTING
▶ GROUND-FAULT
DETECTION I
N
>
▶ 0.4 A to 2000 A
(Set to "0" to disable the
detection function)
▶ SAVE
▶ GROUND-FAULT
DETECTION tI
N
>
▶ 0.04 s to 60 s
▶ SAVE
▶ THRESHOLD
SETTING V
NG
>
▶ 0 % to 100 %
(Set to "0", the ground-fault
detection is based on I
N
>)
▶ SAVE
▶ TIME SETTING
tV
NG
>
▶ 0.04 s to 60 s
▶ SAVE
▶ I
dir
▶ 0.2 A to 30 A
(Set to "0" to disable the
cos ϕ/sin ϕ method)
▶ SAVE
▶ NEUTRAL-POINT
TREATMENT
▶ SOLID or ISOLATED or RESO-
NANT
▶ SAVE
▶ V< ▶ 0 % to 100 %
(Set to "0" to disable the detection function)
▶ SAVE
▶ V> ▶ 0 % to 170 %
(Set to "0" to disable the detection function)
▶ SAVE
▶ PULSE
DETEC-
TION
▶ 3I0 DELTA ▶ 0 % to 300 %
(Set to "0" to disable the
detection function)
▶ SAVE
PULSE
DETEC-
TION
▶ TPULSE ON ▶ 0.50 s to 20 s
(Set to "0" to disable the
detection function)
▶ SAVE
▶ TPULSE OFF ▶ 0.50 s to 20 s
(Set to "0" to disable the
detection function)
▶ SAVE
Parameterization
A.2 Parameterizing the User Interface
86 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019