EasyManua.ls Logo

Siemens SIMATIC CN 4100 - Overview of the Installation

Siemens SIMATIC CN 4100
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
When you connect the shielding to ground on only one side (i.e., at the beginning or end of the
line), you limit attenuation to the lower frequencies.
A one-sided shielding connection may be more suitable in the following cases:
No line for potential equalization can be laid.
Analog signals (some mA or μA) are transmitted.
Foil shields (static shields) are used.
Con󹪝guration
The following 󹪝gure shows the con󹪝guration of the SIMATIC CN 4100 rack with grounded cable
shields.
Grounding screw in grounded state
Metal enclosure of the rack (grounded)
Ethernet port
5.5 Overview of the installation
The procedure described below shows how to install the SIMATIC CN 4100 communication
system.
Requirement
The supply voltage is switched o󹪜.
You are familiar with the basics of installing the SIMATIC CN 4100 communication system.
Notes on installation (Page 21)
Installation
5.5 Overview of the installation
CN 4100 Communication System
28 Equipment Manual, 10/2021, A5E50871363-AA

Table of Contents

Related product manuals