When you connect the shielding to ground on only one side (i.e., at the beginning or end of the
line), you limit attenuation to the lower frequencies.
A one-sided shielding connection may be more suitable in the following cases:
• No line for potential equalization can be laid.
• Analog signals (some mA or μA) are transmitted.
• Foil shields (static shields) are used.
Conguration
The following gure shows the conguration of the SIMATIC CN 4100 rack with grounded cable
shields.
① Grounding screw in grounded state
② Metal enclosure of the rack (grounded)
③ Ethernet port
5.5 Overview of the installation
The procedure described below shows how to install the SIMATIC CN 4100 communication
system.
Requirement
• The supply voltage is switched o.
• You are familiar with the basics of installing the SIMATIC CN 4100 communication system.
Notes on installation (Page 21)
Installation
5.5 Overview of the installation