10.2 Technical speci󹪝cations of components
10.2.1 Technical speci󹪝cations - CPU module
Technical speci󹪝cations TED
Article number 6DL4178-0BH01-0XX0
General information
Product type designation CPU modules 1 slot
HW functional status FS02
Firmware version V1.0
Engineering with
PCS 7 con󹪝gurable/integrated from version
V9.0 SP3
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, max. 400 mA; without USB power supply
Power loss
Power loss, typ. 10 W
Memory
Type of memory Flash
Work memory
integrated
2 Gbyte; ECC
expandable
No
Backup
present
Yes; Entire project maintenance-free in the integral
EEPROM
FB
Number, max.
16 000
Hardware con󹪝guration
Slots
required slots
1
Interfaces
Number of industrial Ethernet interfaces 3
Protocols
Supports protocol for PROFINET IO No
EtherNet/IP No
Modbus TCP Yes
S7 protocol Yes
OPC UA Yes
OPC UA
Technical speci󹪝cations
10.2 Technical speci󹪝cations of components
CN 4100 Communication System
Equipment Manual, 10/2021, A5E50871363-AA 63

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CN 4100 and is the answer not in the manual?

Siemens SIMATIC CN 4100 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CN 4100
CategoryConference System
LanguageEnglish

Related product manuals