Plant changes in RUN - CiR
11.3 Procedure for PROFINET IO
CPU 410 Process Automation/CPU 410 SMART
158 System Manual, 05/2017, A5E31622160-AC
Restriction
All changes that are not explicitly permitted above as part of plant changes in RUN, are not
permitted during operation and are not explained in more detail here.
Recommendations plant changes during operation using CiR
Create a backup copy of your current plant configuration after every modification of the
configuration. Further processing of the project without loss of CiR capability is only
possible with this backup version.
If possible, change the configuration in multiple steps and make only a few changes in
each step. In this way, you can keep track of the changes.
11.3
Procedure for PROFINET IO
11.3.1
Overview
Requirement
You need to load the hardware configuration from HW Config to the module in STOP
Note
You do not have
to define CiR elements in PROFINET IO subsystems.
Procedure
The following basic operating steps are available in RUN mode:
Add or remove IO devices or I/O modules
IO devices and I/O modules can be added and removed in the same step.
Rebuild hardware when adding an IO device
Change process image partition assignment
Re-configure existing modules or I/O modules
Undo previously made changes (Undo functionality)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals