Plant changes in RUN - CiR
11.9 Reconfigure existing modules in ET200M / ET200iSP stations
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
185
3. Repeat steps 1 and 2 for the remaining objects you want to remove.
4. Download the modified configuration to your CPU.
Note
When you delete a slave, STEP
7 updates the guaranteed and the maximum number of
slaves as well as the number of input and output bytes of the associated CiR obj
ect.
When you delete a module in a modular slave of the type ET
200M / ET 200iSP, STEP 7
updates the number of input and output bytes of the associated CiR module.
11.9
Reconfigure existing modules in ET200M / ET200iSP stations
11.9.1
Requirements for Reconfiguration
Note
You can use previously unused channels as well as re
-configure previously used channels.
The addresses of existing modules may not be changed using CiR.
Requirement for configuration
Re-configuration requires an existing CiR object in the respective DP master system.
Hardware requirements
The modules (signal modules and function modules) of the ET 200M / ET 200iSP that can
be re-configured in RUN mode of the CPU are listed in the info text in the "Hardware
catalog" window.
The maximum number of modules that can be re-configured is 100.