Replacement of failed components during redundant operation
13.3 Replacement of components of the distributed I/O on PROFIBUS DP
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
237
Procedure
Proceed as follows to replace a DP slave:
Step
What to do?
How does the system react?
1 Turn off the supply for the DP slave. With one-sided I/O: OB 86 and OB85 are
called for access errors during the PA up-
date.
With switched I/O: OB70 is called (incoming
event), the LED REDF lights up.
2
Remove the bus connector.
3
Replace the DP slave.
4
Plug the bus connector back in and turn the
power supply back on.
The CPUs process the rack failure OB
86 synchronously (outgoing event).
With switched I/O: OB70 is called (out-
going event), the LED REDF goes out.
The associated DP master can address
the DP slave.
13.3.4
Replacement of PROFIBUS DP cables
Starting situation
Failure
How does the system react?
The S7-400H is in redundant system mode and
the PROFIBUS DP cable is defective.
With single-channel one-sided I/O:
Rack failure OB (OB 86) is started (incoming
event). The DP master can no longer process
connected DP slaves
(station failure).
The LED BUS1F flashes.
With switched I/O:
I/O redundancy error OB (OB 70) is started
(incoming event). DP slaves are addressed
via the DP master of the partner.
The LED BUS1F and the LED REDF are
flashing.