Technical data
16.2 Technical specifications of CPU 410E (6ES7410-5HM08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
264 System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HM08-0AB0
• expandable
Dependent on the System Expansion Card used
Load memory
• integrated RAM, max.
48 Mbyte
• expandable RAM
No
Backup
• present
Yes
• with battery
Yes; all data
• without battery
Yes; Program and data of the load memory
Battery
Backup battery
• Backup current, typ.
370 µA; Valid up to 40°C
• Backup current, max.
2.1 mA
• Backup time, max.
Dealt with in the module data manual with the
secondary conditions and the factors of influence
• Feeding of external backup voltage to CPU
No
CPU processing times
CPU speed
450 MHz; Multi-processor system
average processing time of PCS 7 typicals
110 µs; with APL Typicals
Process tasks, max.
9; Individually adjustable from 10 ms to 5 s
CPU-blocks
DB
• Number, max.
16 000; Number range: 1 to 16 000 (= Instances)
FB
• Number, max.
8 000; Number range: 0 to 7999
FC
• Number, max.
8 000; Number range: 0 to 7999
OB
• Number of free cycle OBs
1; OB 1
• Number of time alarm OBs
8; OB 10-17
• Number of delay alarm OBs
4; OB 20-23
• Number of cyclic interrupt OBs
9; OB 30-38 (= Process Tasks)
• Number of process alarm OBs
8; OB 40-47
• Number of DPV1 alarm OBs
3; OB 55-57
• Number of startup OBs
2; OB 100, 102
• Number of asynchronous error OBs
9; OB 80-88
• Number of synchronous error OBs
2; OB 121, 122